|
|
CryoStartUp
Starting Up the βNMR cryostat
Assuming the cryostat is warm (room T) throughout and disconnected from
the Helium dewar, but connected to the temperature controller (heater
and sensor).
0. Schematic Operation:
An schematic diagram (not to scale) is shown below. Liquid helium is
drawn from the "Helium Dewar" to "L He Reservoir" through the "Transfer
Line". A "needle valve" connects the transfer line and the "L He
Reservoir". The valve is used to control the amount of Helium entering
the reservoir and is controlled through the "camp". The transfer
line consists of concentric flow pipes where the outer pipe is
connected to the "counterflow exhaust". The inner line of the tranfer
line is cooled by the counterflow which is connected to a diaphragm
(i.e "Mass flow") pump. The "mass flow" may be controlled and be read
via the "camp".
The liquied Helium reservoir is connected to the sample
space which, in turn, is connected to the powerful Sogevac pump. This
pump is used to cool down the sample.
The arrows inside the tubes/transfer line show the direction of
Helium gas.

1. Preparation
Crane in a He Dewar if necessary. This requires a crane operator
and
some available He dewar (and thus some prior planning). You must open
the hatch in the roof of the cage. Remember to ground the He dewar if
you are going to float the platform.
2. Install the Counter Flow Helium Transfer Line
The transfer line looks like this:

Helium is drawn out of the dewar through the long end of the line into
a reservoir in the cryostat and the cold vapour is drawn back through
the line to the orange rubber hose seen on the right in this picture.
This Helium circulation is accomplished by the small diaphragm pump:

To install the transfer line:
A. Check that you have the correct adapter for the dewar and transfer
line. Check that you have the wooden support for the transfer line.
Have some teflon tape in case the seal is not good. Install the step
ladder if necessary.
B. Make sure the manual needle valve on the inlet side of the transfer
line is open. The Needle Valve is the vertical brass knob, between the
vacuum space pumping port and the counterflow exhaust (orange tube):

B. Slowly introduce the transfer line into the dewar. When there is
some pressure (not to exceed 5 psi) in the dewar, there should be flow
through the line. Remove the protective cover to expose the FRAGILE
cryostat end of the transfer line which looks like this:

You should feel some He gas flowing to the very tip. Once you are sure
this is the case, and that the teflon seal is on the tip as shown,
C. Carefully put the transfer line into the cryostat, by removing the
cap on the port and inserting the tip. If the line gets stuck, try
rotating it about the port. When it is in, tighten the stainless
connector. As the transfer line cools the teflon seal will contract and
the connector nut will need to be tightened again.

D. Connect the white polyflow tube (connected to the diaphragm pump) to
the orange tube at the top of the dewar.
The transfer line is now installed.
3. Make sure the Needle Valve Controller is zeroed.

Go into "setup" and find "zero"

4. Check that there is flow through the cryostat
The cryostat is cooled by pumping a small flow of LHe out of the
reservoir through the automatic needle valve into a capillary leading
to the "block" a sintered piece of copper which is the coldest part of
the operating cryostat. This is done with the high powered Sogevac pump:

A Start up the Sogevac (pumping line assumed connected)
i) Open the Sogevac exhaust to the He return line
(red valve on the right above and valves on the outside of the cage
near the EL3 coldhead)
ii) Turn on the pump with the switch (left
above).
iii) Open the big aluminum handled valve on the pump
inlet - watch the pressure come down on the gauge at the inlet
B. Make sure the cryostat needle valve is closed. Then valve off the
Sogevac. If the NV is not leaking the vacuum gauge should
stay put.
C. Using CAMP, open the NV to 1 turn. Check that the pressure at the
Sogevac climbs to atmosphere. If the transfer line is cold, the
pressure should climb more quickly.
How long should it take for a warm Xfer line (He gas) vs cold Xfer line
for a given NV setting ?
5. Flush the cryostat with He
Repeat the above cycle (4.) a few times, then leave the Sogevac valved
off. This should prevent the NV from clogging with frozen water and/or
air.
6. Start up the diaphragm pump
A Check that it is connected correctly:

B. Make sure the cryostat NV is closed. Switch the diaphragm pump ON
C. In CAMP set some high mass flow value like 30 l/min. With a warm
transfer line, the pump will not be able to pull this rate, but when
the line is cold and liquid is flowing through the flow rate will reach
this value. The flow meter should read some value above its zero (~5
l/min) though.

The transfer line is now cooling. This will take half an hour or so.
Make sure the transfer line is low enough in the dewar to access the
liquid.
After some time the flow rate will get to 30 and the reservoir will
fill. The cold spot on the transfer line port will begin to get cool,
and condensation (and even ice) will form there.
Eventually the orange rubber hose will also frost up, indicating a good
flow of liquid through the line.
7. When the transfer line is cold, begin cooling the cryostat
|
|